TIER ONE TDWS series of Heat Shrink Semi- Conductive Insulation & Double layer Tubing, is used for suitable for applications in power cable joints up to 36kV.

 

Features:

 

Flame retardant

Shrink ratio 3:1

Application up to 36kV

RoHS compliant

 

Technical:

 

Test Items

Test Method

Test Requirements

Insulation layer

 

 

Tensile strength 

ASTM D 2671 

10MPa min.

Ultimate elongation 

ASTM D 2671 

200% min.

Volume resistivity

IEC 93

1014Ω.cm max.

Water absorption

ISO 62

0.5% max.

Semi conductive layer

 

 

Tensile strength 

ASTM D 2671

12MPa min.

Ultimate elongation

ASTM D 2671

200% min.

Volume resistivity

ASTM D 257

104Ω.cm max.

 

Dimensions:

 

(mm)  (mm) (mm) length(m)
  D* (Min.) d*(Max.) w(Min.)   
TDWS 30/12 30 12 5.4 1.0-1.2
TDWS 35/13 35 13 5.4 1.0-1.2
TDWS 45/17 45 17 5.4 1.0-1.2
TDWS 55/21 55 21 5.4 1.0-1.2
TDWS 65/26 65 26 6 1.0-1.2
TDWS 85/30 85 30 6 1.0-1.2
TDWS 100/38 100 38 6 1.0-1.2
TDWS 120/45 120 45 6.1 1.0-1.2

 